PM600 Series Small Format Gas Detection Systems
The PM600 gas detection control panels and detectors are small format systems designed primarily for building services applications. The systems are simple to use and install with precalibrated detector heads. The one and two channel systems are competitively priced for small applications where the PM700 is not necessary. The bright LED display provides clear indication of the system status with two alarm levels and SPCO relays.
Specification
- Power
110/230V AC 15 Watts - Construction
Powder coated mild steel Ral 7000 - Display
4 digit LED; 2 alarm level LED’s; 1 fault LED - Outputs
AL1, AL2, fault SPCO; 8A non inductive built-in audible alarm 60dB - Sealing:
IP54 - Temperature
-5°c to 55°c - Humidity
0-95%RH non condensing
Download PM600 printed information document (pdf).
PM700 Detector Control Panel
The PM700 provides ultimate system flexibility for gas detection systems up to 16 detectors in size. The control panel is compatible with any 4–20mA signal flammable or toxic sensors regardless of manufacturer, which enables us to choose the write sensor to suit each application and gas type. To compliment the system a range of accessories, audio visual alarms are available.
Specification
- Power source
85 to 260 VAC (18 to 30 VDC option) - Power consumption
40 Watts - Display
2 x 16 line backlit - Operating temperature
0°c to 50°c - Operating humidity
Up to 95% non-condensing - Resolution
0.00% or ppm range dependant - Update rate
1 Second - Size (mm)
255 (H) x 265 (W) x 100 (D) - Inputs
Up to 4 or up to 8 x 4–20mA loops - Inputs (optional)
Additional 8 analogue; 4–20mA loops; 1 x RS485 detector data highway for up to 16 detectors
- Outputs (Standard)
1 x solid state visual/flasher 24VDC; 3 x configurable SPCO relays (7 Amp non conductive load); 1 x fault SPCO relays (7 Amp non conductive load); 1 x solid state audio/sounder 24VDC - Outputs (optional)
16 x configurable SPCO relays (7 Amp non conductive load) - Optional equipment Battery backup module:
7AH 255 (H) x 265 (W) x 100 (D) - CE Declaration
EN50081-2: 1994; EN50082-2: 1995; EN61010-1: 2001
Download PM700 printed information document (pdf).
Please forward your details to us via office@pollutionmonitors.co.uk and we will contact you by return to discuss your application in detail.